Out Of Stock
Notify me when its in stock|
Basic |
|
|
Opening Unit Technology |
Thermal Magnetic |
|
Device Application |
Motor |
|
Series |
Tesys |
|
Product Name |
Tesys Gv2 |
|
Product Group |
Gv2Me |
|
Product Series |
Tesys Gv2 |
|
Product or Component Type |
Circuit Breaker |
|
Characteristic |
|
|
Ambient Air Condition for Operating |
-20-60 °C |
|
Operating altitude |
2000 M |
|
Environmental Characteristic for Storage |
-40-80 °C |
|
IK Protection Degree |
Ik04 |
|
IP Protection Degree |
Ip20 'E Conforming to IEC 60529 |
|
Preventive Maintenance |
Th |
|
Standards |
Csa C22.2 No 60947-4-1 |
|
En/Iec 60947-2 |
|
|
En/Iec 60947-4-1 |
|
|
Ul 60947-4-1 |
|
|
Product Certificates |
Atex |
|
Bv |
|
|
Ccc |
|
|
Csa |
|
|
Dnv-Gl |
|
|
Eac |
|
|
Iecee Cb Scheme |
|
|
Lros (Lloyds Register Of Shipping) |
|
|
Rına |
|
|
Ul |
|
|
Flame Vetarder |
960 °C 'E Conforming to IEC 60695-2-1 |
|
General Features |
|
|
[Ics] Rated Service Short-time Breaking Capacity |
100 % -De 230/240 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
40 % -De 400/415 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
50 % -De 440 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
75 % -De 500 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
75 % -De 690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
[In] Rated Current |
25 A |
|
[Ith] Classic Open-air Thermic Current |
25 A 'E Conforming to IEC 60947-4-1 |
|
[Ue] Rated Operating Voltage |
690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
[Ui] Rated Insulation Voltage |
690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
[Uimp] Rated Impulse Withstand Voltage |
6 Kv 'E Conforming to IEC 60947-2 |
|
Opening Unit Degree |
20-25 A |
|
Network Frequency |
50/60 Hz 'E Conforming to IEC 60947-4-1 |
|
Connections-Terminals |
Screw Clamp Terminals 2 Cables 1.5-6 Mm² Flexible Cable Jagless |
|
Screw Clamp Terminals 2 Cables 1-4 Mm² Flexible |
|
|
Screw Clamp Terminals 2 Cables 1-6 Mm² Solid |
|
|
Operating Location |
Anywhere |
|
Depth |
78.5 Mm |
|
Direct Connector |
None |
|
Electric Durability |
100000 Cycles For Ac-3 -De 440 V |
|
Phase Fault Sensibility |
Yes 'E Conforming to IEC 60947-4-1 |
|
Width |
45 Mm |
|
Breaker Capacity |
15 Ka Icu -De 400/415 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
3 Ka Icu -De 690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
4 Ka Icu -De 500 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
50 Ka Icu -De 230/240 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
6 Ka Icu -De 440 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
Control Type |
Opening-Closing Button |
|
Usage Category |
Ac-3 'E Conforming to IEC 60947-4-1 |
|
Category A 'E Conforming to IEC 60947-2 |
|
|
Power Distribution per Pole |
2.5 W |
|
Pole Description |
3P |
|
Magnetic Opening Current |
327-327 A |
|
Maximum Operating Rate |
25 Cyc/H |
|
Mechanical Durability |
100000 Cycles |
|
Motor Power Kw |
11-11 Kw -De 400/415 V Ac 50/60 Hz |
|
15-15 Kw -De 500 V Ac 50/60 Hz |
|
|
Rated Task |
Continuously 'E Conforming to IEC 60947-4-1 |
|
Fixing Mode |
35 Mm Symmetric DIN Rail |
|
Panel: Screwed (With Adaptor Plate) |
|
|
Tightening Torque |
1.7 N.M Above Screw Clamp Terminals |
|
Network Type |
Ac |
|
Compatibility Code |
Gv2Me |
|
Product Weight |
0.26 Kg |
|
Compatibility to Insulation |
Yes 'E Conforming to IEC 60947-1 |
|
Height |
89 Mm |