Out Of Stock
Notify me when its in stock|
Basic |
|
|
[In] Rated Current |
100 A -De 40 °C |
|
Trip Unit Name |
Tm-D |
|
Trip Unit Degree |
40-40 A -De 40 °C |
|
Trip Unit Technology |
Thermal Magnetic |
|
Device Application |
Distribution |
|
Degree Code |
F |
|
Breaking Capacity |
36 Ka Icu -De 440 V Ac 50/60 Hz 'E Confirmation to IEC60947-2 |
|
36 Ka Icu -De 380/415 V Ac 50/60 Hz 'E Confirmation to IEC60947-2 |
|
|
70 Ka Icu -De 220/240 V Ac 50/60 Hz 'E Confirmation to IEC60947-2 |
|
|
Protection Type |
Overload Protection (Thermal) |
|
Short-circuit Protection (Magnetic) |
|
|
Protective Pole Description |
3D |
|
Usage Category |
Category A |
|
Pole Description |
3P |
|
Series |
Easypact |
|
Network Type |
Ac |
|
Earth Lackage Protection |
None |
|
Product Name |
Easypact Cvs |
|
Product Group |
Cv100F |
|
Product Series |
Easypact Cvs100...250 |
|
Product or Component Type |
Circuit Breaker |
|
Classification |
|
|
Environment Condition for Storage |
-50-85 °C |
|
Electric Schock Protection Class |
Class Iı |
|
Ip Protection Degree |
Ip40 |
|
Pollution Degree |
3 'E Confirmation to IEC60664-1 |
|
Rated Operation Environment Temperature |
-25-70 °C |
|
Standards |
En 60947-2 |
|
Iec 60947-2 |
|
|
Product Certificates |
Gost |
|
Iec |
|
|
General Features |
|
|
[Ics] Rated Service Breaking Capacity |
18 Ka -De 440 V Ac 50/60 Hz 'E Confirmation to IEC 60947-2 |
|
36 Ka -De 380/415 V Ac 50/60 Hz 'E Confirmation to IEC 60947-2 |
|
|
70 Ka -De 220/240 V Ac 50/60 Hz 'E Confirmation to IEC 60947-2 |
|
|
[Uimp] Rated Impulse Withstand Voltage |
8 Kv 'E Confirmation to EN/Iec 60947-2 |
|
Instant Pick-up Setting Range |
500A |
|
Instant Pick-up Setting Type Li |
Fixture |
|
Bottom Connection |
Front |
|
Connection Distance |
35 Mm |
|
Connections - Terminals |
Screwed Connection |
|
Depth |
86 Mm |
|
Electrical Durability |
12000 Cycles 415 V In 'E Confirmation to IEC 60947-2 |
|
Width |
105 Mm |
|
Contact Local Signal |
Yes |
|
Control Type |
Transition |
|
Mechanical Durability |
30000 Cycles |
|
Montage Support |
Behind Plaque |
|
Montage Type |
Fixture |
|
Network Frequency |
50/60 Hz |
|
Thermal Protection Adjustment Range |
28-40 A |
|
Compatibility Code |
Cvs100 |
|
Long-Time Pick-up Adjustment Range |
0,7...1 X In |
|
Long-Time Pick-up Adjustment Type Lr |
Adjustable |
|
Long-Time Delay Adjustment Type |
Fixture |
|
Product Weight |
1,8 Kg |
|
Top Connection |
Front |
|
Height |
161 Mm |