Out Of Stock
Notify me when its in stock|
Basic |
|
|
[Icw] Rated Short-Time Withstand Current |
1100 A -De <40 °C - 1 S for Power Circuit |
|
250 A -De <40 °C - 10 S For Power Circuit |
|
|
550 A -De <40 °C - 10 S For Power Circuit |
|
|
950 A -De <40 °C - 10 S For Power Circuit |
|
|
[Ie] Rated Operational Current |
For 200 A 60 °C) -De <= 440 V Ac Ac-1 Power Circuit |
|
[Ith] Classic Open Air Thermic Current |
For 200 A -De <60 °C Signaling Circuit |
|
[Ue] Rated Operational Voltage |
Power Circuit: <= 1000 V Ac 25...400 Hz |
|
Power Circuit: <= 460 V Dc |
|
|
[Ui] Rated Insulation Voltage |
Power Circuit: 1000 V ‘EConforming toıec 60947-4-1 |
|
Power Circuit: 600 V CSA certificated |
|
|
Power Circuit: 600 V UI certificated |
|
|
[Uimp] Rated Impulse Withstand Voltage |
8 Kv 'E Conforming to IEC 60947 |
|
Overvoltage Category |
Iıı |
|
Terminals |
Power Circuit: Connector 1 Cable(s) 10-120 Mm²flexible |
|
Power Circuit: Connector 1 Cable(s) 10-120 Mm²flexible Cable Jagless |
|
|
Power Circuit: Connector 1 Cable(s) 10-120 Mm²Solid Cable Jagless |
|
|
Power Circuit : Connector 2 Cable(s) 10-50 Mm² flexible |
|
|
Power Circuit: Connector 2 Cable(s) 10-50 Mm² flexible Cable Jagless |
|
|
Power Circuit: Connector 2 Cable(s) 10-50 Mm² Solid Cable Jagless |
|
|
Control Circuit: Screw Clamp Terminals 1 Cable(s) 1-2.5 Mm²flexible |
|
|
Control Circuit: Screw Clamp Terminals 2 Cable(s) 1-2.5 Mm²flexible Cable Jagless |
|
|
Control Circuit: Screw Clamp Terminals 1 Cable(s) 1-2.5 Mm²Solid Cable Jagless |
|
|
Control Circuit: Screw Clamp Terminals 2 Cable(s) 1-2.5 Mm²flexible |
|
|
Control Circuit: Screw Clamp Terminals 2 Cable(s) 1-2.5 Mm²flexible Cable Jagless |
|
|
Control Circuit: Screw Clamp Terminals 2 Cable(s) 1-2.5 Mm²Solid Cable Jagless |
|
|
Operating Time |
20…35 Msn Closing |
|
40…75 Msn Opening |
|
|
Electric Durability |
0.8 Mcycles 200 A Ac-1 Ue'De <= 440 V |
|
Level of Security Safety |
B10D = 1369863 Cycles Rated Load Contactor 'E Conforming to En/Iso 13849-1 |
|
B10D = 20000000 Cycles Mechanical Load Contactor 'E Conforming to En/Iso 13849-1 |
|
|
Irms Rated Closing Capacity |
For 140 A Ac Signaling Circuit 'E Conforming to Iec 60947-5-1 |
|
For 250 A Dc Signaling Circuit 'E Conforming to Iec 60947-5-1 |
|
|
Fuse Value |
For 250 A -De 440 V Power Circuit 'E Conforming to Iec 60947 |
|
For 10 A Gg Signaling Circuit 'E Conforming to Iec 60947-5-1 |
|
|
Contactor Application |
Resistor Load |
|
Control Circuit Voltage |
24 V DC |
|
Control Circuit Type |
Dc Standard |
|
Protective Cover |
Yes |
|
Usage Category |
Ac-1 |
|
Power distribution per Pole |
24 W Ac-1 |
|
Fixing Pole Contact |
4 Na |
|
Pole Description |
4P |
|
Maximum Operating Rate |
1200 Cyc/H -De <60 °C |
|
Mechanical Durability |
8 Mcycles |
|
Montage Support |
Plate Block |
|
Rail |
|
|
Rated Breaking Capacity |
1100 A -De 440 V For Power Circuit 'E Conforming to Iec 60947 |
|
Average impedance |
0.6 Mohm - Ith 200 A 50 Hz For Power Circuit |
|
Series |
Tesys |
|
Tightening Torque |
Power Circuit: 12 N.M - Above Connector Hexagon 4 Mm |
|
Power Circuit: 1.2 N.M - Above Screw Clamp Terminals - with Screw Driver Philips No 2 |
|
|
Control Circuit: 1.2 N.M - Above Screw Clamp Terminals - with Screwdriver Philips No 2 |
|
|
Standarts |
Csa C22.2 No 14 |
|
En 60947-4-1 |
|
|
En 60947-5-1 |
|
|
Iec 60947-4-1 |
|
|
Iec 60947-5-1 |
|
|
Ul 508 |
|
|
Product Name |
Tesys D |
|
Product Group |
Lc1D |
|
Product Series |
Tesys D |
|
Product Certificates |
Bv |
|
Ccc |
|
|
Csa |
|
|
Dnv |
|
|
Gl |
|
|
Gost |
|
|
Lros (Lloyds Register Of Shipping) |
|
|
Rına |
|
|
Ul |
|
|
Product or Unit Type |
Contactor |
|
Features |
|
|
Flame Vetarder |
V1 'E Conforming to Ul 94 |
|
Ambient Air Condition for Operating |
-40-60 °C |
|
60-70 °C with derating |
|
|
Operating altitude |
0...3000 M |
|
Environmental Characteristic for Storage |
-60-80 °C |
|
Depth |
132 Mm |
|
Width |
150 Mm |
|
IP Protection Degree |
Ip20 Front 'E Conforming to Iec 60529 |
|
Pollution Degree |
3 |
|
Preventive Maintenance |
Th 'E Conforming to Iec 60068-2-30 |
|
Mechanical Robustness |
Shocks Contactor Open: 11 Msn for 10 Gn |
|
Shocks Contactor Close: 11 Msn for 15 Gn |
|
|
Vibrations Contactor Open: 2 Gn, 5...300 Hz |
|
|
Vibrations Contactor Close: 4 Gn, 5...300 Hz |
|
|
Product Weight |
2.86 Kg |
|
Fire Endurance |
850 °C 'E Conforming to IEC 60695-2-1 |
|
Heigh |
158 Mm |
|
General Features |
|
|
Bobin Technology |
Without built-in suppressor module |
|
Contact Compatibility |
M8 |
|
Control Circuit Voltage Limits |
0,15...0,4 Uc -40-70 °C Reduce Ac 50/60 Hz |
|
0,75...1,2 Uc -40-55 °C Operating Ac 50 Hz |
|
|
1...1,2 Uc -55-70 °C Operating Ac 60 Hz |
|
|
Compatibility Code |
Lc1D |
|
Inrush Power in W |
270-365 W 20 °C |
|
Hold Power Consumption in W |
2.4-5.1 W -De 20 °C) |
|
Time Fixture |
25 Ms |