Out Of Stock
Notify me when its in stock|
Basic |
|
|
[Icw] Rated Short-Time Withstand Current |
1100 A -De <40 °C - 1 S for Power Circuit |
|
250 A -De <40 °C - 10 S For Power Circuit |
|
|
550 A -De <40 °C - 1 S For Power Circuit |
|
|
950 A -De <40 °C - 10 S For Power Circuit |
|
|
100 A - 1 S for Signaling Circuit |
|
|
120 A - 500 Ms for Signaling Circuit |
|
|
140 A - 100 Ms for Signaling Circuit |
|
|
[Ie] Rated Operational Current |
For 200 A 60 °C) -De <= 440 V Ac Ac-1 Power Circuit |
|
For 115 A 60 °C) -De <= 440 V Ac Ac-3 Power Circuit |
|
|
[Ith] Classic Open Air Thermic Current |
For 200 A -De <60 °C Signaling Circuit |
|
[Ue] Rated Operational Voltage |
Power Circuit: <= 1000 V Ac 25...400 Hz |
|
Power Circuit: <= 300 V Dc |
|
|
[Ui] Rated Insulation Voltage |
Power Circuit: 1000 V ‘EConforming toıec 60947-4-1 |
|
Signaling Circuit: 690 V CSA certificated |
|
|
Power Circuit: 600 V CSA certificated |
|
|
Power Circuit: 600 V UI certificated |
|
|
Signaling Circuit: 600 V UI certificated |
|
|
Signaling Circuit: 600 V CSA certificated |
|
|
Signaling Circuit: 690 V Conforming to IEC 60947-1 |
|
|
[Uimp] Rated Impulse Withstand Voltage |
8 Kv 'E Conforming to IEC 60947 |
|
Overvoltage Category |
Iıı |
|
Terminals |
Power Circuit: Connector 1 Cable(s) 10-120 Mm²flexible |
|
Power Circuit: Connector 1 Cable(s) 10-120 Mm²flexible Cable Jagless |
|
|
Power Circuit: Connector 1 Cable(s) 10-120 Mm²Solid Cable Jagless |
|
|
Power Circuit : Connector 2 Cable(s) 10-50 Mm² flexible |
|
|
Power Circuit: Connector 2 Cable(s) 10-50 Mm² flexible Cable Jagless |
|
|
Power Circuit: Connector 2 Cable(s) 10-50 Mm² Solid Cable Jagless |
|
|
Control Circuit: Screw Clamp Terminals 1 Cable(s) 1-2.5 Mm²flexible |
|
|
Control Circuit: Screw Clamp Terminals 2 Cable(s) 1-2.5 Mm²flexible Cable Jagless |
|
|
Control Circuit: Screw Clamp Terminals 1 Cable(s) 1-2.5 Mm²Solid Cable Jagless |
|
|
Control Circuit: Screw Clamp Terminals 2 Cable(s) 1-2.5 Mm²flexible |
|
|
Control Circuit: Screw Clamp Terminals 2 Cable(s) 1-2.5 Mm²flexible Cable Jagless |
|
|
Control Circuit: Screw Clamp Terminals 2 Cable(s) 1-2.5 Mm²Solid Cable Jagless |
|
|
Operating Time |
20…50 Msn Closing |
|
6…20 Msn Opening |
|
|
Electric Durability |
0.8 Mcycles 200 A Ac-1 Ue'De <= 440 V |
|
0.95 Mcycles 115 A Ac-3 Ue'De <= 440 V |
|
|
Level of Security Safety |
B10D = 1369863 Cycles Rated Load Contactor 'E Conforming to En/Iso 13849-1 |
|
B10D = 20000000 Cycles Mechanical Load Contactor 'E Conforming to En/Iso 13849-1 |
|
|
Irms Rated Closing Capacity |
For 1260 A -De 440 V Signaling Circuit 'E Conforming to Iec 60947-5-1 |
|
For 140 A Ac Power Circuit 'E Conforming to Iec 60947-5-1 |
|
|
For 250 A Dc Signaling Circuit 'E Conforming to Iec 60947-5-1 |
|
|
Fuse Value |
For 250 A -De 440 V Power Circuit 'E Conforming to Iec 60947 |
|
200 A Gg -De <= 690 V Power Circuit for Coordination Type 2 |
|
|
For 10 A Gg Signaling Circuit 'E Conforming to Iec 60947-5-1 |
|
|
Contactor Application |
Resistor Load |
|
Motor Control |
|
|
Control Circuit Voltage |
42 V Ac 50/60 Hz |
|
Control Circuit Type |
Ac -De 50/60 Hz |
|
Protective Cover |
Yes |
|
Usage Category |
Ac-1 |
|
Ac-3 |
|
|
Ac-4 |
|
|
Power distribution per Pole |
24 W Ac-1 |
|
7.9 W Ac-3 |
|
|
Fixing Pole Contact |
3 Na |
|
Pole Description |
3P |
|
Maximum Operating Rate |
2400 Cyc/H -De <60 °C |
|
Mechanical Durability |
8 Mcycles |
|
Montage Support |
Plate Block |
|
Rail |
|
|
Rated Breaking Capacity |
1100 A -De 440 V For Power Circuit 'E Conforming to Iec 60947 |
|
Motor Power HP |
100 Hp -De 575/600 V Ac 50/60 Hz for 3 Phase Motors |
|
30 Hp -De 200/208 V Ac 50/60 Hz for 3 Phase Motors |
|
|
40 Hp -De 230/240 V Ac 50/60 Hz for 3 Phase Motors |
|
|
75 Hp -De 460/480 V Ac 50/60 Hz for 3 Phase Motors |
|
|
Motor Power KW |
18.5 Kw -De 400 V Ac 50/60 Hz (Ac-4) |
|
30 Kw -De 220...230 V Ac 50/60 Hz (Ac-3) |
|
|
55 Kw -De 380...400 V Ac 50/60 Hz (Ac-3) |
|
|
59 Kw -De 415...440 V Ac 50/60 Hz (Ac-3) |
|
|
65 Kw -De 1000 V Ac 50/60 Hz (Ac-3) |
|
|
75 Kw -De 500 V Ac 50/60 Hz (Ac-3) |
|
|
80 Kw -De 660...690 V Ac 50/60 Hz (Ac-3) |
|
|
Average impedance |
0.6 Mohm - Ith 200 A 50 Hz For Power Circuit |
|
Series |
Tesys |
|
Tightening Torque |
Power Circuit: 12 N.M - Above Connector Hexagon 4 Mm |
|
Power Circuit: 1.2 N.M - Above Screw Clamp Terminals - with Screw Driver Philips No 2 |
|
|
Control Circuit: 1.2 N.M - Above Screw Clamp Terminals - with Screwdriver Philips No 2 |
|
|
Standarts |
Csa C22.2 No 14 |
|
En 60947-4-1 |
|
|
En 60947-5-1 |
|
|
Iec 60947-4-1 |
|
|
Iec 60947-5-1 |
|
|
Ul 508 |
|
|
Product Name |
Tesys D |
|
Product Group |
Lc1D |
|
Product Series |
Tesys D |
|
Product Certificates |
Bv |
|
Ccc |
|
|
Csa |
|
|
Dnv |
|
|
Gl |
|
|
Gost |
|
|
Lros (Lloyds Register Of Shipping) |
|
|
Rına |
|
|
Ul |
|
|
Product or Unit Type |
Contactor |
|
Auxiliary Contact Fixing |
1 Na + 1 Nk |
|
Features |
|
|
Flame Vetarder |
V1 'E Conforming to Ul 94 |
|
Ambient Air Condition for Operating |
-40-60 °C |
|
60-70 °C with derating |
|
|
Operating altitude |
0...3000 M |
|
Environmental Characteristic for Storage |
-60-80 °C |
|
Depth |
136 Mm |
|
Width |
120 Mm |
|
IP Protection Degree |
Ip20 Front 'E Conforming to Iec 60529 |
|
Pollution Degree |
3 |
|
Preventive Maintenance |
Th 'E Conforming to Iec 60068-2-30 |
|
Mechanical Robustness |
Shocks Contactor Open: 11 Msn for 10 Gn |
|
Shocks Contactor Close: 11 Msn for 15 Gn |
|
|
Vibrations Contactor Open: 2 Gn, 5...300 Hz |
|
|
Vibrations Contactor Close: 4 Gn, 5...300 Hz |
|
|
Product Weight |
2.5 Kg |
|
Fire Endurance |
850 °C 'E Conforming to IEC 60695-2-1 |
|
Heigh |
158 Mm |
|
General Features |
|
|
Bobin Technology |
Built-in bidirectional peak limiting diode suppressor |
|
Heat Distrubition |
3-8 W -De 50/60 Hz |
|
Non-overlapping time |
In 1.5 Ms Blackout Power Between Nk Ve Na Contact |
|
In 1.5 Ms Energization Between Nk Ve Na Contact |
|
|
Contact Compatibility |
M13 |
|
Control Circuit Voltage Limits |
0,3...0,5 Uc -40-70 °C Reduce Ac 50/60 Hz |
|
0,8...1,15 Uc -40-55 Operating Ac 50/60 Hz |
|
|
1...1.5 Uc 55-70 °C Operating Ac Ac 50/60 Hz |
|
|
Compatibility Code |
Lc1D |
|
Inrush Power in Va |
280-350 Va 50 Hz 0.8 20 °C) |
|
280-350 Va 60 Hz 0.8 20 °C) |
|
|
Hold Power Consumption in Va |
2-18 Va 50 Hz 0.3 20 °C) |
|
2-18 Va 60 Hz 0.3 20 °C) |
|
|
Minimum Switching Current |
For 5 Ma Signaling Circuit |
|
Minimum Switching Voltage |
For 17 V Signaling Circuit |
|
Motor Starter Type |
Direct On-Line Contactor |
|
Signaling Circuit Frequency |
25...400 Hz |
|
Auxiliary Contact Type |
Type is Mirror Contact 1 Nk 'E Conforming to IEC 60947-4-1 |
|
Type is connected as mechanical 1 Na + 1 Nk 'E Conforming to Iec 60947-5-1 |
|